Features
• Six Zones
• Selectable control mode [PID or On/Off] each zone
• Selectable cooling control mode [On/Off only] each zone
• 20 Segment Profile for each zone
• Selectable number of active zones
• Adjustable Display Time
• Field Proven Zone Switching
• Temperature and Setpoint Monitoring
• Four Digit Display of Temperature
• 1 Digit Display of Zones
• 5 Amp Latching or Non-Latching Relay
• Standard Thermocouples [T,E,J,K,S,R,B,C]
• Extended Ranges
• Programmable Selection of HI, LO or HI/LO Alarms
• Password Protection
• 1/4 DIN Aluminum Box
• Splash Proof Face
• Plug-In I/O Terminals
• RS-232 Communication
SPECIFICATIONS
| No. of
Zones
|
Six |
| Input Range
|
0-40mV Standard/0-75mV
Expanded |
| Accuracy
|
±0.1% Range ±1 °C |
| Resolution
|
±5uV |
| Thermocouple Input
|
selectable
B,C,E,J,K,R,S,T |
| Scale
|
Selectable °C or °F |
| PID
|
Autotune or Manual |
| Password
protection
|
Yes |
| Profiling [ramp /
soak]
|
20 segments per loop |
| Control outputs
|
6 [one per loop] |
| Output rating :
|
Internal power 5V DC
10 Ma max |
| External power
|
5 to 40V DC 0.5 Amp |
| Communication
|
RS-232 |
|
|
Thermocouple
Ranges
Standard Ranges
TC
ºC
Range
J
0-750
K
0-1000
E
0-500
T
0-400
S
0-1750
R
0-1750
B
0-1800
N
0-1100
C
0-2300
Extended Ranges
K
0-1300
E
0-1000
RTD Ranges
100W Platinum
0-600
120W Nickel
0-300
10W Copper
0-250
Description
|
ºF Range
32-1400
32-1900
32-1000
32-750
32-3200
32-3200
32-3300
32-2100
32-4200
32-2500
32-1800
32-1200
32-600
32-500
|
Models
The following Models are available:
- Standard Thermocouple
- Extended Range
Model Number Description
CN616TC1 - Standard Thermocouple
CN616TC2- Extended Range Thermocouple
|
|
The CN616 Series is a second generation of industrial temperature controllers based on the field proven
CN600 six
zone temperature monitor/alarm system.
Two models are available, standard and extended
range. The CN616 Series is a
microprocessor based temperature controller, which
accepts signals from thermocouples. Six zones are sequentially
scanned at 15 readings per second [@ 60 Hz] and displayed
with a selectable display rate of 1 to 40 seconds each zone.
A single output relay is provided to indicate an alarm condition on any
one zone. Six PID time proportional or on/off outputs are
provided to control six zones. The faceplate has been arranged to
call attention to an alarm condition by flashing the main temperature display and indicating the zone in alarm with a
flashing zone number display. The CN616
Series implements a security password to
protect all functions.
|
| Communication
Software
|
Visual Basic [Windows] |
| Zone display time
|
Settable 1- 40 sec or
Hold on any zone |
| Alarms
Selectable
|
HI - LO - HI/LO
or no alarms |
| Alarm Type
|
Latching or Non
Latching |
| Alarm display
|
Flashing display
[zone in alarm] |
| Alarm output [deenergises
on alarm]
|
Single relay for
all zones |
| Alarm Reset
|
Manual |
| Relay rating
|
5 Amp @ 120 VAC |
| Display
|
LED 0.6"
high |
| Enclosure
|
1/4 Din
Aluminum, 6" long |
| Terminals
|
Headers for
Plug-in Wiring |
| Line Power
|
120/240VAC;
50/60Hz |
| Power
Consumption
|
10VA Max. |
| Max. Volts
between Inputs
|
6VDC or RMS |
| Open T/C Warning
|
Flashing Display
[9999] |
|