Features
• Six Zones
• Adjustable Display Time
• Field Proven Zone Switching
• Temperature and Setpoint Monitoring
• Four Digit Display of Temperature
• 2 Digit Display of Zones
• 5 Amp Latching or Non-Latching Relay
• Standard Thermocouples [T,E,J,K,S,R,B,C]
• Extended Ranges
• Six RTD Inputs (2 or 3 wire)
• Six Optional Independent Outputs
• Programmable Selection of HI, LO or HI/LO Alarms
• Password Protection
• Optional Inputs Other Than Thermometer
• 1/4 DIN Aluminum Box
• Splash Proof Face
• Plug-In I/O Terminals
• RS-232 Communication
SPECIFICATIONS
| No. of
Zones
|
Six |
|
Zone Display Time Adjust.
|
1-40 seconds |
|
Scan Time
|
Approx. 1/4 sec |
|
Input Range
|
0-40mV Standard/0-75mVExpanded |
|
Accuracy
|
±0.1%Range ±1 °C |
|
Resolution
|
±5uV |
|
Thermocouple Type
|
J,K,E,T,S,R,B,C |
|
Cold Junction Compensation
|
Automatic |
|
Linearity
|
±1 °C |
|
Scale Selectable
|
°C or °F |
|
Open T/C Warning
|
Flashing Display |
|
RTD (2 or 3 wire)
|
100W
Pl,
100W Ni,
10W Cu |
|
|
Thermocouple
Ranges
Standard Ranges
TC
ºC
Range
J
0-750
K
0-1000
E
0-500
T
0-400
S
0-1750
R
0-1750
B
0-1800
N
0-1100
C
0-2300
Extended Ranges
K
0-1300
E
0-1000
RTD Ranges
100W Platinum
0-600
120W Nickel
0-300
10W Copper
0-250
Description
|
ºF Range
32-1400
32-1900
32-1000
32-750
32-3200
32-3200
32-3300
32-2100
32-4200
32-2500
32-1800
32-1200
32-600
32-500
|
Models
The following Models are available:
- Standard Thermocouple
- Extended Range
- RTD Input
Model Number Description
CN606TC1 6 Zone T/C
CN606TC2 6 Zone T/C w/Extended Range
CN606RTD 6 Zone RTD (2 Wire)
CN606RTD-C 6 Zone RTD (2 Wire) Copper
CN606RTD-3 6 Zone RTD (3 Wire)
CN606RTD-3C 6 Zone RTD (3 Wire) Copper
(Open Collector Option - 6 Alarm)
CN606TC1-OC 6 Zone T/C
CN606TC2-OC 6 Zone T/C w/Extended Range
CN606RTD-OC 6 Zone RTD (2 Wire)
CN606RTD-OC-C 6 Zone RTD (2 Wire) Copper
|
|
The CN606 Series is a second generation of industrial scanners based on the field proven
CN600 six zone temperature
monitor/alarm system. Several models and options are available.
The CN606 Series is a microprocessor based
scanner which accepts signals from thermocouples or RTD's. In the basic
unit, six zones are sequentially scanned with a selectable display
rate of 1 to 40 seconds each. A single output relay is provided to
indicate an alarm condition on any zone. The faceplate has been arranged to call
attention to an alarm condition by flashing
the main temperature display and indicating the zone in alarm with a flashing zone number display. To
prevent alarm on startup, Lo alarm is not activated until all
enabled zones cross Lo alarm setpoint. The CN606 Series implements a security
password to protect certain functions.
|
|
Line Power
|
120/240VAC; 50/60Hz |
|
Power Consumption
|
10VA Max. |
|
Alarm Relay
|
5 Amp; 120VAC
Relay deenergizes on alarm |
| Opt.
6 Outputs (One/Zone; Open Collector Transistors deenergize on
alarm)
|
5 MA 5 V
Internal
0.5Amp@40VDC
External
DC power required |
|
Communication
|
RS232 (3wire) |
|
Alarms Selectable
|
HI,
LO,
HI/LO |
|
Alarm Range
|
Full Range |
|
Terminals
|
Headers for Plug-in Wiring |
|
Enclosure
|
1/4 Din Aluminum, 6" long |
|
Reset
|
Manual |
|
Max. Volts
between Inputs
|
Inputs 6VDC or RMS |
|
Reaction to Power Loss
|
Unit returns to "RUN" MODE |
|
Main Display
|
Four Digit; 0.6" high |
|